R-Value to U-Value Converter

Introduction to R-value, U-factor, and insulation performance

R-value measures resistance to conductive heat flow. In the imperial system used by many North American product labels and building codes, its unit is ft²·°F·h/Btu. A larger R-value means that heat crosses the layer more slowly. U-value, also called U-factor or thermal transmittance, describes the rate of heat transfer in Btu/(ft²·°F·h). A smaller U-value therefore indicates better thermal performance.

This calculator converts either measurement into its reciprocal, reports the equivalent metric value, and estimates steady-state heat flux for a selected indoor-to-outdoor temperature difference. The scale provides context for the result. The optional Assembly Builder then goes beyond a single uniform layer by comparing an insulated cavity path with the lower-resistance framing path that causes thermal bridging.

Enter a positive R-value, or leave this field blank and enter a positive U-value.

Enter a positive U-value, or leave this field blank and enter a positive R-value.

Enter a positive indoor-to-outdoor temperature difference for the heat-flux estimate. A blank field uses 50 degrees Fahrenheit.

Enter an R-value or U-value to convert.

Copy status messages appear here.

The converted value is also reported in the result panel above.

Assembly Builder: stack layers until the wall U-factor beats the target

Assembly Builder applies the same reciprocal arithmetic to a framed wall. Each layer is drawn at a thickness-related scale, while the calculator tracks a cavity path and a wood-stud path. Cavity insulation improves only the insulated path; continuous insulation improves both. Animated arrows make the greater heat flow through framing visible. Clear each level by providing an interior finish, cavity insulation, and cladding while staying under the target U-factor, depth limit, and budget.

Level 1

Target U-factor 0.084

Assembly U

Effective R

Cavity path R 0.85

Stud path R 0.85

Framing factor 25%

Depth used 0.00 / 5.50 in

Cost $0.00 / $6.50

Score 0

Best 0

Assembly Builder reports cavity-path R-value, stud-path R-value, area-weighted U-factor, wall depth, and cost. Use the adjacent controls if canvas interaction is unavailable.

Press Start build, then stack layers from the inside out. Every wall needs an interior finish, cavity insulation, and cladding before it can be signed off.

Keyboard, after focusing the wall: and select a material; and change thickness; Enter or Space adds it; Backspace removes the last layer; and N advances after a win. With a pointer or touch, select a palette chip, select it again to cycle thickness, drag it into the wall, or tap an installed layer to remove it.

  • Air films apply to both paths
  • Cavity fill helps the cavity path
  • Wood framing forms a thermal bridge
  • Continuous layers help both paths
  • Arrow density follows heat flow
  • Solid and dashed lines show path temperature profiles
Wall layer ledger, beginning at the interior face
Layer Thickness (in) Cavity-path R Stud-path R Cost ($/ft²)
Assembly total 0.00 0.85 0.85 0.00

The model uses R-1.25 per inch for softwood framing, an R-0.68 interior air film, and an R-0.17 exterior air film. Its assembly U-factor is an area-weighted parallel-path result rather than the reciprocal of the cavity insulation alone.

How to use the R-value and U-value converter

Enter a positive number in either the R-value field or the U-value field, leaving the other one blank. Editing one field clears the other so there is only one authoritative input. Select Convert to calculate the reciprocal. The result uses imperial units by default; select the SI option to add RSI in m²·K/W and metric U-value in W/(m²·K). Reset clears the inputs, result, scale, and shareable query parameter.

The temperature difference, ΔT, does not change the R-to-U conversion. It is used only for the heat-flux estimate. Enter the difference between the warm and cold sides of the surface, not either temperature by itself. For example, 70 °F indoors and 20 °F outdoors gives ΔT = 50 °F. The resulting heat flux is expressed per square foot, so finding total conductive heat transfer requires multiplying that figure by the relevant surface area.

Formulas for reciprocal thermal resistance and heat flow

For a uniform layer or a single complete path under steady-state conditions, thermal transmittance is the reciprocal of thermal resistance:

Formula: U = 1 / R R = 1 / U

U=1R R=1U

Layers arranged in series are crossed one after another, so their R-values add. U-values should not be added or averaged for those layers:

Formula: R_total = R_1 + R_2 + ⋯ + R_n U_assembly = 1 / (∑ i = 1 n R_i)

Rtotal=R1+R2++Rn Uassembly=1i=1nRi

Once U and the temperature difference are known, steady-state heat flux is:

Formula: q = U × Δ T

q=U×ΔT

The calculator converts imperial R-value to metric RSI with the standard unit factor:

Formula: R_SI = 0.1761 × R_IP

RSI=0.1761×RIP

Worked example: comparing a U-0.28 window with R-3.2

Suppose one replacement window is rated U-0.28 and another is described as R-3.2. Converting the first product gives 1/0.28 ≈ 3.57. Because R-3.57 is greater than R-3.2, the U-0.28 window has the lower conductive heat transfer. The difference is modest, and a purchase decision should also consider air leakage, solar heat gain, installation quality, and climate.

For an opaque example, R-13 corresponds to U ≈ 0.0769. With ΔT = 50 °F, its idealized heat flux is about 3.85 Btu/(h·ft²). A 100 ft² uniform surface would therefore conduct roughly 385 Btu/h under those steady conditions. A framed wall cannot be treated as a uniform R-13 layer because the studs provide a second, more conductive route.

Thermal bridging and the parallel-path wall formula

A wood-framed wall has at least two parallel paths. One crosses the insulation-filled cavities; the other crosses studs, plates, headers, and other framing. The framing factor is the fraction of wall area assigned to the stud path. Each path has its own total resistance, and the path U-values are weighted by area:

Formula: U_assembly = f_frame / R_stud + (1 − f_frame) / R_cavity R_effective = 1 / U_assembly

Uassembly=fframeRstud+1fframeRcavity Reffective=1Uassembly

Consider a 2×6 wall with R-20.4 cavity insulation, R-0.45 gypsum, R-0.55 sheathing, R-0.61 siding, and interior and exterior air films totaling R-0.85. The cavity path is about R-22.9. Replacing the cavity insulation with 5.5 inches of softwood at R-1.25 per inch gives a stud path near R-9.3. At a 25% framing factor, the result is approximately U-0.060, or effective R-16.7. That is substantially weaker than the batt label suggests.

Continuous exterior insulation raises both path resistances. Adding R-6 continuous insulation to the example produces paths near R-28.9 and R-15.3, reducing the weighted U-factor to about U-0.042. This is why code descriptions such as “R-20 + R-5 continuous insulation” distinguish cavity insulation from material that covers framing.

Common insulation values and result interpretation

Material performance depends on product density, temperature, aging, moisture, and testing method, so design documents should use the manufacturer’s tested value. The ranges below are useful for checking whether an input is plausible.

Approximate thermal resistance of common materials
MaterialTypical R per inchApproximate reciprocal U
Fiberglass battR-3.2 to R-3.8U-0.31 to U-0.26
Expanded polystyreneR-4.0U-0.25
Extruded polystyreneR-5.0U-0.20
Closed-cell spray foamR-6.0 to R-6.5U-0.17 to U-0.15
Softwood framingAbout R-1.25About U-0.80

Reciprocal performance has diminishing returns. Increasing R-10 to R-20 cuts ideal conductive heat flow in half, from U-0.10 to U-0.05. Increasing R-40 to R-50 changes U from 0.025 to 0.020, a smaller absolute reduction. That does not make high insulation levels useless, but it does mean that air sealing, window performance, equipment efficiency, and moisture durability should be considered alongside added R-value.

Climate, installation, and retrofit guidance for R-values

Climate-zone requirements differ because heating, cooling, condensation, and solar conditions vary. Codes may specify cavity R-value, continuous insulation, or a maximum whole-assembly U-factor. Always check the locally adopted code rather than treating a general climate table as an approval. A target may also differ for walls, roofs, floors, windows, and doors.

In retrofits, seal uncontrolled air paths before assuming that more insulation will solve every comfort problem. Gaps around penetrations, rim joists, attic bypasses, and poorly installed windows can carry heat and moisture around insulation. Batts should fill cavities without gaps or compression. Foam products need compatible flashing and fire protection, while assemblies in cold or humid climates require a moisture-control strategy appropriate to their drying direction.

International R-value and U-value units

Imperial R-value uses ft²·°F·h/Btu, while metric thermal resistance, often called RSI, uses m²·K/W. Multiply imperial R by 0.1761 to obtain RSI. Thus R-19 is about RSI 3.35. Metric U-value uses W/(m²·K); an imperial U-factor is multiplied by about 5.678 to obtain that value. The reciprocal relationship remains valid only when R and U use matching unit systems.

Limitations and assumptions of this R/U conversion

The basic converter assumes steady-state, one-dimensional conduction through a uniform layer or a path whose total R-value is already known. It does not independently model air leakage, solar gain, thermal mass, radiant barriers, changing outdoor temperatures, moisture transport, fasteners, balconies, steel framing, or three-dimensional junctions. The heat-flux result is a rate per unit area, not an annual energy prediction.

The Assembly Builder is educational rather than a permit-ready simulation. It uses simplified material values, two idealized parallel paths, fixed air films, and a framing factor. Complex projects should use tested product data and an accepted whole-building or whole-assembly method such as ASHRAE procedures or ISO 6946. Confirm compliance with the authority having jurisdiction and seek professional advice where condensation, fire safety, or structural details are significant.

Sources: The reciprocal, series-layer, air-film, and parallel-path methods are described in the ASHRAE Handbook—Fundamentals and ISO 6946. Material testing is addressed by ASTM C518. See also the U.S. Department of Energy’s insulation guidance, the 2021 IECC residential provisions, and NIST unit guidance.

R-value and U-value questions people ask

Is U-value always 1 divided by R-value?

Yes for one uniform layer or one complete thermal path expressed in matching units. It is not enough to invert the cavity insulation label and call that a framed wall’s U-factor. The wall has parallel framing and cavity paths, so their U-values must be weighted by area.

Can R-values from different layers be added?

Yes, when heat crosses those layers in series. Add drywall, insulation, sheathing, continuous insulation, and applicable surface films as resistances, then invert the total. Do not add their U-values.

Why do windows usually list U-factor?

A window rating represents the conductance of glass, gas spaces, spacers, and frame as a complete product. Lower U-factor means less conductive heat transfer. U-0.30 is equivalent to about R-3.33.

Why can cavity insulation stop producing large whole-wall gains?

Studs remain a lower-resistance path regardless of how much insulation fills the adjacent bay. Once that path dominates the weighted result, continuous insulation is more effective because it also covers the framing.

Does a higher R-value guarantee lower energy bills?

No. It reduces ideal conductive heat flow through the treated area, but actual savings also depend on climate, air leakage, windows, equipment, controls, utility prices, workmanship, and the amount of surface upgraded.

Embed this calculator

Copy and paste the HTML below to add the R-Value to U-Value Converter with Heat Flux and Wall Builder to your website.