Understanding home heating loads
A furnace size (often expressed as BTU per hour, or BTU/h) is essentially a practical way to match your home’s heat loss rate on a cold design day. Your home constantly loses heat through walls, ceilings, floors, windows, doors, and air leakage. A properly sized furnace supplies heat at roughly the same rate so indoor temperatures stay stable without excessive cycling.
This calculator provides a rule-of-thumb estimate based on three inputs that strongly influence heating demand:
- Heated (conditioned) area in square feet
- Climate zone (as a proxy for winter severity)
- Insulation/air-sealing quality (as a proxy for envelope performance)
It also uses your furnace efficiency to translate between required heat delivered to the house (output BTU/h) and the fuel input rating (input BTU/h) you see on furnace spec sheets.
How the estimate works (method overview)
The core idea is a heating “factor” in BTU/h per square foot. Industry sizing rules of thumb compress many variables (outdoor design temperature, insulation levels, air leakage, window area, etc.) into a single approximate factor. The calculator:
- Selects a base factor from your climate zone.
- Adjusts it with an insulation multiplier.
- Multiplies by heated area to estimate required heat output (BTU/h).
- Converts output BTU/h to an approximate furnace input rating using efficiency (AFUE).
Base heating factors by climate zone
These typical starting points are widely used “quick estimate” factors. Real homes can be meaningfully above or below them.
| Climate zone |
Representative areas |
Base factor (BTU/h·ft²) |
| Zone 1 (South) | Very warm winter climates | 30 |
| Zone 2 | Warm / mild winter climates | 35 |
| Zone 3 | Mixed climates | 40 |
| Zone 4 | Cool winter climates | 45 |
| Zone 5 | Cold winter climates | 50 |
| Zone 6 | Very cold winter climates | 55 |
| Zone 7 (North) | Severe winter climates | 60 |
Insulation (and air-sealing) adjustment
Insulation quality is used as a proxy for the combined effects of insulation levels and air leakage:
- Good: multiplier 0.8 (better insulation/air sealing → lower heat loss)
- Average: multiplier 1.0 (typical baseline)
- Poor: multiplier 1.2 (older/drafty → higher heat loss)
Adjusted factor = base factor × insulation multiplier.
Formulas used
1) Required heat output (delivered to the home)
Output BTU/h is estimated from area and the adjusted factor:
- Q = required furnace output (BTU/h)
- A = heated area (ft²)
- Fadj = adjusted factor (BTU/h·ft²)
2) Furnace input rating estimate (what many furnace model numbers reflect)
If efficiency is entered as AFUE (%), then:
This helps you compare your calculated need to common furnace sizes (e.g., 60k, 80k, 100k input BTU/h).
3) Optional cost estimate (if provided)
If you enter a cost per 1,000 BTU, the calculator can estimate a simple hourly cost based on the estimated output:
- Hourly cost ≈ (Q ÷ 1,000) × cost_per_1000
Note: this is a rough proxy and not a substitute for fuel-utility pricing (therms, kWh) and real seasonal runtime.
How to interpret the results
- Output BTU/h is the heat you want delivered into the home at peak conditions. If the calculator shows ~45,000 BTU/h output, you’re generally looking for a furnace that can deliver roughly that amount on the coldest design days.
- Input BTU/h is the fuel input rating. With a 90% AFUE furnace, 50,000 BTU/h output corresponds to about 55,600 BTU/h input (50,000 ÷ 0.90).
- Sizing to available equipment: furnaces come in discrete sizes. You typically select the nearest available size that meets the design requirement, but avoid jumping far above the estimate unless a qualified load calc supports it.
- Oversizing vs. undersizing:
- Oversized systems can short-cycle (more starts/stops), create temperature swings, reduce comfort, and in some cases reduce efficiency.
- Undersized systems may run continuously and may not maintain setpoint during extreme cold snaps.
Worked example
Scenario: A 2,000 ft² home in Climate Zone 5 with average insulation, considering a 92% AFUE furnace.
- Area A = 2,000 ft²
- Base factor (Zone 5) = 50 BTU/h·ft²
- Insulation multiplier (Average) = 1.0
- Adjusted factor Fadj = 50 × 1.0 = 50
- Estimated output Q = 2,000 × 50 = 100,000 BTU/h output
- Estimated input = 100,000 ÷ 0.92 ≈ 108,700 BTU/h input
Interpretation: You’d likely compare models around ~110k input BTU/h (depending on what’s available) and then validate with a proper load calculation—especially if the home has high ceilings, lots of glass, significant air leakage, or zoning.
Quick comparison: how insulation changes the estimate
The same home and climate zone can land in a very different range depending on envelope quality.
| Assumption set |
Multiplier |
Adjusted factor (BTU/h·ft²) |
Output for 2,000 ft² (BTU/h) |
| Good insulation / tight envelope |
0.8 |
40 |
80,000 |
| Average |
1.0 |
50 |
100,000 |
| Poor insulation / drafty |
1.2 |
60 |
120,000 |
Limitations & assumptions (important)
- Rule-of-thumb model: This calculator uses generalized BTU/ft² factors. It is not a replacement for an ACCA Manual J load calculation.
- Ceiling height not included: Homes with tall ceilings or multiple stories may require different sizing because volume and stack-effect infiltration can increase loads.
- Windows and glazing not modeled: Large window areas, older single-pane windows, and skylights can significantly raise heat loss.
- Air leakage is simplified: Draftiness, duct leakage, and pressure imbalances can materially change real heating needs.
- Basement/attic conditions vary: Heated basements, unconditioned basements, slab-on-grade, and attic insulation levels all affect heat loss.
- Local design temperatures vary within zones: Elevation, wind exposure, and microclimates can move the real load up or down.
- Equipment selection details: Final furnace sizing should consider duct capacity, static pressure, blower performance, and manufacturer output ratings at installation conditions.
When to call a pro: If you’re purchasing new equipment, planning major insulation/air-sealing upgrades, adding conditioned space, or your current system has comfort issues, an HVAC contractor or energy auditor can run a Manual J (and duct assessment) to confirm the correct size.